ThermoFLUX DC inverter heat pumps use R290 refrigerant with an extremely low global warming potential (GWP) of only 3. As an eco-friendly solution, R290 is ideal for high-temperature heating applications in cold climates. Quick and easy installation in just one day — can be mounted on floor, wall, or roof.

Features

Technology of the future

— 01

Eco-Friendly R290

Refrigerant with GWP of only 3 — up to 700 times lower environmental impact than traditional refrigerants.
— 02

CAREL Touch Controller

Smart 4.3" touch screen controller with sensors that automatically track all environmental changes.
— 03

Wi-Fi control

Control the device via app and enjoy online support no matter where you are.
— 04

Panasonic Compressor

Rotary compressor that operates at low frequency after reaching desired temperature, reducing consumption.
— 05

Grundfos pump

High-quality Grundfos circulation pump for reliable and efficient heat distribution.
— 06

Flexible installation

Installation in just one day — on floor, wall, or roof, without complications.

Advantages

Other features

Premium components from world-leading manufacturers for maximum reliability and efficiency.
  • R290 refrigerant with GWP 3
  • CAREL 4.3″ touch screen controller
  • Panasonic rotary compressor
  • Grundfos circulation pump
  • SANHUA four-way walve
  • Plate heat exchanger
  • CAREL electronic expansion valve
  • Wi-Fi monitoring and online support
  • Floor, wall, or roof mounting

Technical details

Detailed overview of specifications for all models
TF11 CT 220V TF15 CT 220V TF18 CT 220V TF15 CT 400V TF18 CT 400V
Power supply V/Hz/Ph 220-240/50/1 220-240/50/1 220-240/50/1 380-420/50/3 380-420/50/3
Refrigerant R290 R290 R290 R290 R290
Max. heating capacity (1) kW 11 15 18 15 18
COP (1) 4.43 4.45 4.46 4.41 4.46
Heating capacity min./max. (1) kW 5.06 / 11.00 6.90 / 15.00 8.28 / 18.00 6.90 / 15.00 8.28 / 18.00
Heating input power min./max. (1) W 952 / 2483 1292 / 3371 1304 / 3401 1547 / 4036
COP min./max. (1) 4.43 / 5.32 4.45 / 5.34 4.46 / 5.35 4.41 / 5.29 4.46 / 5.35
Max. heating capacity (2) kW 10.6 14.4 17.3 14.4 17.3
COP (2) 3.54 3.56 3.57 3.53 3.57
Heating capacity min./max. (2) kW 4.86 / 10.56 6.62 / 14.40 7.95 / 17.28 6.62 / 14.40 7.95 / 17.28
Heating input power min./max. (2) W 1202 / 2980 1632 / 4045 1954 / 4843 1647 / 4082 1954 / 4843
COP min./max. (2) 3.54 / 4.04 3.56 / 4.06 3.57 / 4.07 3.53 / 4.02 3.57 / 4.07
Max. cooling capacity (3) kW 10.0 13.7 16.4 13.7 16.4
EER (3) 3.44 3.45 3.46 3.42 3.46
Cooling capacity min./max. (3) kW 4.61 / 10.03 6.29 / 13.68 7.55 / 16.42 6.29 / 13.68 7.55 / 16.42
Cooling input power min./max. (3) W 1166 / 2918 1582 / 3962 1894 / 4743 1597 / 3997 1894 / 4743
EER min./max. (3) 3.44 / 3.96 3.45 / 3.98 3.46 / 3.99 3.42 / 3.94 3.46 / 3.99
Max. cooling capacity (4) kW 7.1 9.6 11.6 9.6 11.6
EER (4) 2.75 2.76 2.77 2.74 2.77
Cooling capacity min./max. (4) kW 3.25 / 7.08 4.44 / 9.65 5.33 / 11.58 4.49 / 9.65 5.33 / 11.58
Cooling input power min./max. (4) W 934 / 2573 1268 / 3492 1518 / 4181 1280 / 3524 1518 / 4181
EER min./max. (4) 2.75 / 3.48 2.76 / 3.50 2.77 / 3.51 2.74 / 3.47 2.77 / 3.51
Rated load kW 3.72 5.06 6.05 5.1 6.05
Max. input power A 17.82 24.19 28.97 10.77 12.78
Power cable cross-section mm² 6 6 6 4 4
Fuse A 32A 40A 40A 20A 20A
Noise level (1m) dB(A) 46 46 46 46 47
Noise level dB(A) 60 60 60 60 61
CO₂ equivalent tona 3.30 3.96 4.62 3.96 4.62
ErP Level (35°C) A+++ A+++ A+++ A+++ A+++
Net dimensions (LxWxH) mm 1110*475*960 1110*475*1355 1110*475*1355 1110*475*1355 1110*475*1355
Net packaging dimensions (LxWxH) mm 1165*490*1100 1165*490*1520 1165*490*1520 1165*490*1520 1165*490*1520
Net weight kg 105 124 124 124 124
Gross weight kg 120 150 150 150 150
Swipe

Notes:

Sheet metal type: Weather-resistant PP + galvanized steel + ASA

(1) Heating conditions: water inlet/outlet temperature: 30°C/35°C, Ambient temperature: DB 7°C/WB 6°C
(2) Heating conditions: water inlet/outlet temperature: 40°C/45°C, Ambient temperature: DB 7°C/WB 6°C
(3) Cooling conditions: water inlet/outlet temperature: 23°C/18°C, Ambient temperature: DB 35°C/WB 24°C
(4) Cooling conditions: water inlet/outlet temperature: 12°C/7°C, Ambient temperature: DB 35°C/WB 24°C